Safe is safe:
Quality check
for transformers.

Better safe than sorry: quality check for transformers.

Home 9 Services & Benefits 9 Test fields for transformers
In our modern testing facilities, we put the entire range of reconditioned transformers through their paces before delivery. In addition, we offer comprehensive special tests - according to your requirements and specifications. For permanently reliable function and the best possible safety.

Our services at a glance:

  • Special test bay for the final testing of transformers
  • Testing of transformers with secondary voltage of 110 kV and total weight of up to approx. 100 t
  • Standard performance of the following tests:
  • Insulation resistance measurement
  • Measurement of the winding resistance in milliohm
  • High voltage test at 50 Hz
  • Idle measurement
  • Short circuit measurement
  • Checking the voltage ratio (transmission test)
  • Oil analysis
  • Customized execution of the following work:
  • Coil testing
  • Testing the switching devices
  • Checking the functions of the control and regulating units
  • Partial discharge and Tandelta measurements (PD – tan δ)
  • Flash pulse measurements

An overview of our available voltage sources:

Power supply
Voltage [V]
Current [A]
Alternating current (50 Hz)
3 x 0 - 30,000 V
10 A
Alternating current (50 Hz)
3 x 0 - 400 V
2.000 A
Alternating current (50 Hz)
3 x 0 - 1,000 V
400 A
Alternating current (50 Hz)
3 x 0 - 3,000 V
400 A
Alternating current (50 Hz)
3 x 0 - 6,000 V
400 A
Alternating current (50 Hz)
3 x 0 - 12,000 V
400 A
Alternating current (50 Hz)
1 x 0 - 200,000 V
-
Available frequencies: 16 - 120 Hz

Important questions about transformer testing

How is the testing program for a repaired transformer determined?

We tailor the program to the transformer type, nominal values, scope of repair, applicable regulations, and required acceptance testing. Standard tests are supplemented with customer- or damage-specific measurements as needed. The scope, limit values, and documentation are agreed upon before the test date.

What do open-circuit and short-circuit measurements show on a transformer?

No-load measurement provides information about the magnetic circuit and no-load losses, while short-circuit measurement describes, among other things, impedance and load-dependent losses. Deviations can indicate winding, connection, or core problems. The evaluation is carried out by comparison with target, type, or previous measured values.

What information do measurements of the translation and winding resistance provide?

The translation test checks whether the voltage ratio and switching position are plausible. Winding resistances can indicate contact problems, unbalanced connections, or winding deviations. Temperature, measurement method, and reference values ​​must be considered during interpretation.

When are partial discharge or lightning impulse tests useful?

These specialized tests are used depending on the voltage level, design, scope of repair, damage hypothesis, and required verification. They answer different questions than resistance or translation measurements and require a suitable, low-noise setup. We tailor the benefits, load, and acceptance criteria to each specific project.

What specifications do we need for a customer-specific transformer acceptance test?

Required information includes nominal and circuit data, relevant standards, agreed-upon tests, limit values, and the desired documentation format. Previous test reports and customer-specific specifications facilitate comparison. Any open questions are clarified before assembly and testing to ensure the results are clearly evaluable.